MENSAJE DE AGREGAR AL CARRITO
OnlineKit

PANEL 12 ZONAS DET. 12 LEDS, 4 CIRC.SEÑAL. COM.DIGITAL FUENTE 5 AMP

MI-FA301-12LDR

Description

PANEL DE ALARMA Y DETECCION DE INCENDIOS CON PANTALLA LED DE 12 ZONAS MIRCOM
Marca: MIRCOM
Modelo: FA301-12LDR

-12 LEDs Bicolores para Alarma & LEDs Ambar indicadore de Problemas
-12Circuitos Indicadores de Alarma IDC Clase "B" (Estilo B) con Switches de By-pass.
-4 Circuitos de Notificación de Alarma NAC (1.7Amps), Clase "B"( Estilo Y) con Switches de By-pass
-Comunicador Digital & Modem, UDACT de 2 lineas
-Soporta Anunciador de Alarma y Registro de Eventos
-Fuente de Alimentación 5 Amp ( Circuito de Notificación & Auxiliar )
-Configurable desde el frente del Panel o Mediante Laptop
-Gabinete Negro con puerta Roja

-El FA-301-12LDR está equipado con un comunicador UDACT / Digital incorporado. Se pueden usar dos módulos convertidores ICAC-306 Seis circuitos de iniciación Clase “A” para el cableado de Clase “A” (Estilo “D”) de los circuitos de iniciación.
-Se puede usar un módulo convertidor de clase de circuito “A” de cuatro circuitos de indicación OCAC-304 para el cableado de clase “A” (estilo “Z”) de los circuitos de indicación.
-El FA-301-12LR y el FA-301-12LDR son configurables por el teclado (usando la herramienta de configuración CFG-300) para la programación en el sitio o por una PC para la programación en el sitio y remota.
-El gabinete soportará hasta 12 baterías AH. Los paneles pueden ser montados parcialmente con el anillo embellecedor FA-UNIV-TRB opcional.
-Entrada de CA
-120VAC @ 60Hz / 240VAC @ 50Hz
-Energía de reserva
-Baterías de reserva 24VDC
-Capacidad de carga 10 AH

Listed to UL 864, 9th edition
Integrated UDACT/Digital Communicator on select models
2 line by 20 character back-lit LCD display
Front panel and PC programmable
Remote upload/download capabilities
Class “B” (Style “B”) initiating circuits,configured as Class “A” (Style “D”) using a Class “A” converter module
Initiating circuits may be configured as Alarm, Verified Alarm, Waterflow Alarm, Sprinkler Alarm, Latching or Non-Latching Supervisory, Monitor and Trouble-Only
Audible signals configured for Steady, Temporal Code, California Code and March Time
Indicating Circuits configurable as Silenceable or Non-Silenceable for both signals and strobes
Built-in sync strobe protocols: Mircom, Amseco, System Sensor, Gentex, Faraday and Wheelock
Relay contacts for Common Alarm, Auxiliary/Alarm (Disconnectable), Common Supervisory and Common Trouble
Configurable Signal Silence Inhibit, Auto Signal Silence and One-Man Walk Test
Subsequent Alarm, Supervisory, and Trouble operation
RS-485 Interface for Remote LED Annunciators,
Interface for a Remote Trouble Indicator (RTI)
200 event alarm log
5 Amp Power Supply
Optional modules for additional internal relay circuits and City Tie/Polarity Reversal
ORDER INFORMATION

FA-301-12DDR
Twelve Zone LCD Display Fire Alarm Control Panel with built-in UDACT/Digital Communicator

FA-300TRB
Black Semi-Flush Trim Ring for FA-300-6 Enclosures

FA-UNIV-TRB
Black Universal Semi-Flush Trim Ring

FA-300-DF
Dead Front for FA-300-6DR/FA-300-6DDR

FA-301-DF
Dead Front for FA-301-12DDR
Circuitos de indicación

-Potencia limitada / 24 VCC sin filtro / 1.7 A a 49 ° C por circuito. Máximo 5 amperios.
-Suministro auxiliar (no resetable)
-Potencia limitada / 22.3VDC regulado / 500mA máx.
-Suministro de humo de 4 hilos (reajustable)
-Potencia limitada / 22.3VDC regulado / 300mA máx.
-Suministro no filtrado (onda completa rectificada)
-Potencia limitada / 24 VCC sin filtro / 1.7 A máx. A 49 ° C
-Relés auxiliares (Alarma común / supv / trb / y alarma secundaria auxiliar) FormC / 28VDC / 1A max.
-Modelo FA-301-8L (D) FA-301-12L (D) 136mA en espera (96 mA *) 164mA (104 mA *)
-Alarma 366mA (326 mA *) 424mA (364 mA *)
  * Uso de resistencias de fin de línea activas (consulte el manual de instalación y operación para obtener más información)

Details